Figure 25-1:
Single tube with condensate drain
DC-1449
Installation notes (continued)
t
Orient dispersion tube with tubelets (steam orifices) pointing up.
t *GNPVOUJOHUIFIVNJEJGJFSBCPWFUIFMFWFMPGEJTQFSTJPOUVCF
see “Drip tee installation” on Page 18.
t 5BCMFMJTUTIPTFLJUTJ[FTCZIVNJEJGJFSNPEFM/PUFUIBUUIF
capacities of models 30 and 34 require multiple tube assemblies
and cannot use a hose kit. For multiple tube assemblies, see
“Rapid-sorb,” beginning on Page 26.
%JTQFSTJPO
4JOHMFUVCF
Single dispersion tube with condensate drain
Mounting nut
M10
Humidi-tech humidifier
Duct
Secure and seal
escutcheon plates
90° long sweep
or two 45° elbows
Pitch tube toward
drain 1%
DN15 condensate drain tube.
Pitch 2%
toward escutcheon plate.
DN20 (minimum) condensate drain tube by installer.
Must be suitable 100 °C water.
DN8
150 mm
recommended
Water seal
125 mm
25 mm
air gap
Steam hose, tubing or pipe. Insulate
tubing and hard pipe to reduce steam
loss. Do not insulate steam hose. See
Table 16-1 for maximum piping lengths.
Pitch*
Open drain required. Locate air gap only in spaces with adequate
temperature and air movement to absorb flash steam; otherwise,
condensation may form on nearby surfaces. Refer to governing codes for
drain pipe size and maximum discharge water temperature.
Installation
Dashed lines indicate provided by installer.
See the first bullet in
Installation notes.
OM-351-1
82.5 mm
82.5 mm
Condensate drain
A
Dispersion tube
Dimension A:
tNNGPS%/UVCFT
tNNGPS%/UVCFT
A
Escutcheon plates
Table 25-1:
Hose kit sizing by model
HT
model
Hose kit
(vapor hose,
dispersion tube,
and hardware)
Maximum capacity
of dispersion tube
(kg/h)
2 – 8
DN40
hose kit
without drain
13
10 – 16
DN40
hose kit
with drain
25.8
DN50
hose kit
without drain
25.8
21 – 25
DN50
hose kit
without drain
38.6
30 – 34
These models require multiple tube
assemblies and cannot use a hose kit.
* Pitch steam hose, tubing, or pipe toward humidifier:
– 15% when using steam hose
– 5% when using DN40 tubing or pipe
– 2% when using DN50 tubing or pipe