Specifications

5
MOUNTING THE HUMIDI-TECH
®
Electrical power supply, water make up piping and
drain piping must also be considered. Electrical
power supply connections are made at the lower or
upper right rear corner of the unit. Water makeup
and draining piping connections are made at the
lower left rear corner.
When mounting on a stud wall (studs 405 mm
centres), locate studs and position coach screws in
place so that each of the screws (405 mm apart) will
center on a stud. Mark hole locations and pre-drill
6 mm diameter pilot holes using mounting template
on the HUMIDI-TECH box. Secure frame to wall with
coach screws provided.
For hollow block or poured concrete wall mounting,
position template in place and mark the holes. Drill
appropriate pilot hole for two 10 mm toggle bolts or
two 10 mm machine bolt lead anchors. Secure frame
in place.
Locating and mounting the
HUMIDI-TECH humidifier
The HUMIDI-TECH humidifier is designed to lag bolt
to the wall, and it should be installed in a space
located near an air duct system.
Consider the following when selecting the location of
the humidifier:
• Convenient access to duct
• Electrical and plumbing connections
• Required clearances
• External water seal requirements
The mounting location should provide a minimum
clearance of 915 mm to the front and 610 mm to the
right side of the unit. This clearance is required for
removing the evaporating chamber and accessing
electrical compartment. Also, a minimum clearance
of 150 mm to the left side is required for louvers and
enclosure fasteners.