Specifications

7
HUMIDI-TECH
®
PIPING
Notes:
Offset humidifier from spill funnel or floor drain to prevent flash steam from rising into the cabinet.
Dashed lines indicate provided by installer.
The water supply inlet is more than 25 mm above the skim/overflow port, eliminating the possibility of
backflow or siphoning from the tank. No additional backflow prevention is required, however, governing
codes prevail.
Install a union in the water supply line as shown to allow tank removal.
Shock arrester
recommended to
reduce water hammer
DN10 (3/8") connection to water
supply line; water pressure must be
between 175 kPa and 550 kPa;
water conductivity minimum
100 μS/cm
Water supply line
Spill funnel.
Plumb to
floor drain
25 mm
air gap
DN20 (¾") tank
drain, skimmer and
P-trap piping, rated
for 100°C. If piping
run is over 3 m
increase pipe to
DN32 after P-trap.
Open floor drain.
Refer to governing
codes for drain pipe
size and maximum
temperature requirements.
Cover
Electrical conduit
knockouts provided
top and bottom:
Combination, with
knockout diameters
of 22.3 mm and
28.6 mm
Combination, with
knockout diameters
of 28.6 mm and
34.9 mm
Install level
Steam vapor hose
(maximum run 3 m).
May also use pipe or
tubing.
DC-1136
DN20 (¾")
frame drain and
P-trap piping, rated for
100°C
Two keyholes for wall
mounting, 406 mm
on center
300 mm
50 mm
HUMIDI-TECH (standard water) field piping overview
Frame drain
Unions by installer