Specifications
13
HUMIDI-TECH
®
DISPERSION
Drip tee installation
Install a drip tee as shown below when the humidi-
fier is mounted higher than the dispersion device,
when interconnecting hose or piping needs to go
over an obstruction, or when interconnecting piping
runs are long. IMPORTANT: Vapor hose must be
supported to prevent sagging or low spots.
Obstruction
Pitch: 1%
HUMIDI-TECH
humidifier
Tubing or pipe drip tee, by
installer. DRI-STEEM part
numbers for 304 stainless steel
inline tees:
• DN40: No. 162710
• DN50: No. 162712
Funnel or floor drain.
Refer to governing codes for drain
pipe size and maximum temperature
requirements.
25 mm
air gap
200 mm minimum
150 mm recommended
To dispersion
device
DC-1450
Dashed lines indicate
provided by installer.
DN20
90° long sweep or
two 45° elbows
Insulate tubing
and hard pipe to
reduce steam loss
Steam loss of interconnecting vapor
hose, tubing and pipe
Maximum steam carrying capacity and
length of interconnecting vapor hose,
tubing and pipe*
Notes:
* Based on total maximum pressure drop in hose,
tubing or piping of 1250 Pa
** Maximum recommended length for vapor hose is 3 m.
Longer distances may cause kinking or low spots.
*** To minimize loss of capacity and efficiency, insulate
tubing and piping.
†
Developed length equals measured length plus 50%
of measured length, to account for pipe fittings.
Note:
This data is based on an ambient air temperature of 27 °C,
fiberglass insulation, copper tubing and schedule 40 pipe.
Vapor hose
Copper or stainless steel tubing
and Schedule 40 steel pipe
Hose
I.D.
(DN)
Maximum
capacity
(kg/h)
Maximum
length**
(m)
Tube
or pipe
size***
(DN)
Maximum
capacity
(kg/h)
Maximum
developed
length
†
(m)
40 68 3 40 68 6.1
50 113 3 50 100 9.2
Description
Nominal
hose,
tubing
or pipe size
Steam loss
Insulation
thickness
Noninsulated Insulated
DN kg/h/m kg/h/m mm
Hose
40 0.220 N/A N/A
50 0.300 N/A N/A
Tubing
40 0.164 0.030 50
50 0.210 0.037 50
Pipe
40 0.330 0.030 50
50 0.380 0.037 50
HT(HT)_IOM_Metric.pdf 13 1/18/2010 1:42:04 PM