Installation guide

1BHFt%3*45&&.7BQPSMPHJD
3
Installation and Operation Manual
Main menu: Diagnostics screen
Diagnostics
The Diagnostics screen allows you to monitor all of the analog and
discrete inputs to the Vapor-logic
3
control system. Use the Next and
Back to scroll through the input signals on your system.
The Diagnostics screen is useful when troubleshooting. For
example, to troubleshoot the RH signal input, select RH Signal
on the Diagnostics screen. The screen displays the input signal in
milliamps and what this signal translates to in terms of relative
humidity. You then can verify that the input is working correctly.
The table below lists available Diagnostic menu items (depending
on system options and type) with normal values and/or ranges.
Table 78-1:
Diagnostics menu items
Display item Normal values and/or ranges
RH input
Configuration string
X 4 mA to 20 mA 0% to 100% % RH
Demand
input
E 4 mA to 20 mA 0% to 100% % demand
H 0 VDC to 10 VDC 0% to 100% % demand
D 6 VDC to 9 VDC 0% to 100% % demand
/ Open or closed 0% or 100% % demand
C 0 to 150 ohms 0% to 100% % demand
L Demand input not displayed.
Dew point input 4 mA to 20 mA 0 °F to 100 °F –17 °C to 37 °C
Duct HL input Open or closed
Temp comp input 4 mA to 20 mA –20 °F to 160 °F –28 °C to 71 °C
High probe voltage 7"$/PXBUFS 0.0 VAC Water
Mid probe voltage 7"$/PXBUFS 0.0 VAC Water
Low probe voltage 7"$/PXBUFS 0.0 VAC Water
DI float 7"$/PXBUFS 0.0 VAC Water
Tank temp input 0 to 2120 ohms –240 °F to 265 °F –151 °C to 129 °C
Airflow switch Open or closed
Safety interlock Open or closed
GTS only
Model 100* 300* 200, 400, 600, 800*
Blower 1 rpm 0 to 3000 rpm 0 to 5800 rpm
Blower 2 rpm 0 to 4800 rpm 0 to 5800 rpm
Blower 3 rpm 0 to 5800 rpm
Blower 4 rpm 0 to 5800 rpm
Burner 1 gas valve Open or closed
Burner 2 gas valve Open or closed
Burner 3 gas valve Open or closed
Burner 4 gas valve Open or closed
Combustion air switch Open or closed
Power vent switch Open or closed
Notes for Table 78-1:
* Blower speeds listed in this table are for
GTS04 models. GTS99 models have the
GPMMPXJOHCMPXFSTQFFET
(54SQN
(54SQN
(54(54(54(54
0-5200 rpm
VL3_IOM.pdf 82 11/19/2009 9:11:16 AM