Installation guide
DRI-STEEM Vapor-logic
3
*OTUBMMBUJPOBOE0QFSBUJPO.BOVBMt1BHF
Service interval
The Vapor-logic
3
controller tracks the amount of water converted
to steam by the humidifier. When the amount of water converted to
steam exceeds the Service set point (a user-defined amount of water
in pounds or kilograms adjusted in the system Set Up screen), the
“Service Humidifier” message appears on the Idle screen.
The humidifier continues to operate after the message appears.
The message notifies the user that the service interval was reached
and the humidifier should be cleaned. To remove the “Service
Humidifier” message from the Idle screen and reset the Service
Interval, press Enter when viewing the “Water til Service” parameter
in the Set Up menu.
Setting date and time
The Vapor-logic
3
controller contains a real-time clock that is used
for several features including the drain and flush sequence and the
logging of alarms. If you need to reset the date or time, both are
accessible through the Set Up screen. The date and time will need to
be reset whenever the Vapor-logic
3
controller has been powered off
for a length of time.
4FSWJDFJOUFSWBMTFUUJOHEBUFBOE
time
VL3_IOM.pdf 81 11/19/2009 9:11:16 AM