Installation and Operation Manual
Transmitter control
With transmitter control, the Vapor-logic
3
board receives a linear
signal that corresponds to the actual humidity level measured
in the space being controlled. (With a transmitter provided by
DRI-STEEM, the signal is 4 to 20 mA, which corresponds to
0 to 100% RH). The Vapor-logic
3
controller employs an internal
PID loop that uses this humidity measurement along with a
user–defined humidity set point to calculate a demand level. This
demand level is the level at which the humidifier will run. For more
information on the PID control loop, refer to Page 66.