Installation guide
1BHFt%3*45&&.7BQPSMPHJD
3
Installation and Operation Manual
Table 64-1:
Set Up menu information
Set Up menu parameter Set Up menu description Range Default
ADS Day Day to start ADS sequence Sunday (1) through Saturday (7) 1
ADS Hour Hour to start ADS sequence UPNJEOJHIUUPQN 0
ADS Interval /VNCFSPGEBZTCFUXFFO"%4DZDMFT 1 day to 180 days 1 day
ADS Duration Auto drain sequence duration 0 minutes to 120 minutes
4ZTUFNEFQFOEFOU
STS 14 mins.
GTS 18 mins.
Vaporstream
12 mins.
Vapormist, CRUV,
Humidi-tech
8 mins.
AFS Duration Auto flush sequence duration 0 minutes to 15 minutes 1 minute
Service Setpoint Service interval set point
100 lbs to 3,276,700 lbs (100 kg to
1,486,300 kg)
System dependent
Water til Service
Amount of water remaining until service interval
is met
Enter key resets service interval /"
Skim Duration Skim time duration 0 seconds to 120 seconds
4ZTUFNEFQFOEFOU
STS 35 seconds
GTS 40 seconds
Vaporstream
30 seconds
Vapormist, CRUV,
Humidi-tech
9 seconds
Heater Cycle Time (TP-type control) Cycle time 30 seconds to 99 seconds 60 seconds
Heater Cycle Time (SSR-type control) Cycle time 1 second to 30 seconds 2 seconds
SDU Area-type Duration
How long the fan runs after there is no call for
humidity
5 minutes to 30 minutes 5 minutes
Aquastat Aquastat set point 40 °F to 180 °F (4 °C to 82 °C) 40 °F (4 °C)
Inactivity Until EOS
Inactivity time until end-of-season drain cycle
starts
1 hour to 168 hours 72 hours
Set Up Password Password required to enter the Set Up screen 0 to 255 (0 = password disabled) 0
Configuration String See configuration string section in this manual System dependent System dependent
%BUF5JNF Date and time settings /" Current date/time
Idle Time
Keypad inactivity duration until the idle screen
appears
Off to 1000 minutes 5 minutes
Note:
t:PVSTZTUFNNBZOPUIBWFBMMPGUIFTFSFBEPVUT
Main menu: Set Up screen,
continued
VL3_IOM.pdf 68 11/19/2009 9:11:15 AM