Installation and Operation Manual
Table 40-1 (continued):
LonTalk network variable outputs (nvo) available with Vapor-logic
3
nvo SNVT Description
nvoAlarm 4/75@BMBSN
/PUF
See Pages 61-62 for fault
definitions.
These outputs are expressed using a 64-bit map. The user will see a 64-bit number of 1s and 0s. For
FYBNQMFJGUIFSFJTBMPXMFWFMQSPCFGBVMUUIFVTFSXJMMTFFBiwJOUIF[FSPQPTJUJPOPGUIFCJUNBQ
1000000000000000000000000000000000000000000000000000000000000000
Bit map positions 0–30 are identified below; bit map positions 31–63 are for factory use only; disregard
TUBUFTJOQPTJUJPOToUIPTFQPTJUJPOTJEFOUJmFECZBO9GPSFYBNQMF
000000000000000000000000000000XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
'PSDVTUPNFSTXJUIWFSTJPOYY5DIJQTOWP"MBSNJTEJWJEFEJOUPUXPCJUNBQTOWP"MBSN#.@BOE
OWP"MBSN#.@1PTJUJPOTPGOWP"MBSNBSFUIFTBNFBTQPTJUJPOTPGOWP"MBSN#.@1PTJUJPOT
PGOWP"MBSNBSFUIFTBNFBTQPTJUJPOTPGOWP"MBSN#.@
Description Position Description Position
Low level probe fault 0 Drain fault 16
Mid level probe fault 1 Tank level fault 17
Fill fault 2 Probe assembly fault 18
Thermal trip 3 Tank temp fault 19
Burner 1 fault 4 Boil time fault 20
Ignitor 1 fault 5 Burner 3 fault 21
Blower 1 fault 6 Ignitor 3 fault 22
Burner 2 fault 7 Blower 3 fault 23
Ignitor 2 fault 8 Burner 4 fault 24
Blower 2 fault 9 Ignitor 4 fault 25
Flue fault 10 Blower 4 fault 26
SDU fault 11 Gas valve 1 fault 27
RH transmitter fault 12 Gas valve 2 fault 28
DP transmitter fault 13 Gas valve 3 fault 29
VAV transmitter fault 14 Gas valve 4 fault 30
Temp transmitter fault 15 Factory use 31–63
OWP%JHJUBM@*0 4/75@TUBUF
These main board digital input states are expressed using a 16-bit map. See the table on the next page.
-PO5BML/FUXPSLWBSJBCMFPVUQVUT
OWPDPOUJOVFE