Table 39-1:
LonTalk network variable outputs (nvo) available with Vapor-logic
3
nvo SNVT Description
nvoTimeStamp 4/75@UJNF@TUBNQ Read the current date and time that the unit is set to.
nvoMode 4/75@DPVOU 3FBEUIFDVSSFOUNPEFPGUIFVOJU5IFEFmOFEPQUJPOTBSF
1. Auto
2. Standby
3. Drain (manual)
OWP4QBDF@3) 4/75@MFW@QFSDFOU Read the relative humidity content of the air in the space being humidified (percent RH).
OWP4QBDF@41 4/75@MFW@QFSDFOU Read the humidity set point for the space being humidified (percent RH).
OWP%VDU@3) 4/75@MFW@QFSDFOU Read the relative humidity content of the air in the duct. Valid only when a duct mounted transmitter is
installed.
OWP%VDU@41 4/75@MFW@QFSDFOU Read the humidity set point for the duct. This is the maximum RH that the unit will allow the duct to get to.
See the ”VAV control“ section o
n Page 70 for more information.
nvoEstSteamPcnt 4/75@MFW@QFSDFOU Read the estimated amount of steam the humidifier is producing as a percentage of total capacity.
OWP&TU4UFBN-C@)S 4/75@DPVOU Read the estimated amount of steam the humidifier is producing in pounds per hour.
nvoGlassTemp 4/75@UFNQ@Q Read the window glass temperature.
nvoEnergyInPcnt 4/75@MFW@QFSDFOU Read the amount of energy being consumed as a percentage of the humidifier's total capacity.
nvoTankTemp 4/75@UFNQ@Q Read the temperature of the water in the humidifier's evaporating chamber.
nvoLbsH2OTilADS 4/75@DPVOU Read the pounds of water remaining to be converted to steam before the next automatic drain sequence
(ADS) cycle.
nvoTotalSteam 4/75@DPVOU Read the pounds of water that have been converted to steam since this counter was reset.
nvoWaterTilSrvc 4/75@DPVOU Read the pounds of water remaining to be converted to steam before the next service cycle.