Installation guide
1BHFt%3*45&&.7BQPSMPHJD
3
Installation and Operation Manual
Control cabinet installation and wiring
The Vapor-logic
3
control board is shipped mounted with all
internal wiring completed within a control cabinet. All software is
custom programmed into your Vapor-logic
3
system according to
the original order requirements. Some control cabinets are factory
mounted on the humidifier. Vapormist and Humidi-tech control
components are located under the shroud.
Important control cabinet installation points
t "MMIVNJEJGJFSQPXFSXJSJOHJTSFQSFTFOUFEPOUIFIVNJEJGJFS
wiring diagram located on the inside of the control cabinet door
along with an installation guide. Return all instructions to the
control cabinet after installation.
t "MTPSFGFSUPUIF7BQPSMPHJD
3
control board connection
information o
n Pages 11–14 of this manual for detail of the board
and connection
points.
t *GUIFDPOUSPMDBCJOFUJTOPUGBDUPSZNPVOUFEQJDLBMPDBUJPOUIBU
allows easy access to the control cabinet and internal electrical
components
t .PVOUDPOUSPMDBCJOFUVTJOHUIFNPVOUJOHUBCTVOMFTTDBCJOFUJT
factory mounted or is integral to the humidifier).
t "MXBZTXJSFUIF7BQPSMPHJD
3
control board per governing codes.
t 7BQPSMPHJD
3
is powered by a low voltage Class 2 control
transformer. The transformer provides a 24 VAC supply and is
protected by an integral manual reset circuit breaker.
t 'PMMPXGJFMEXJSFUPSRVFSFRVJSFNFOUTTIPXOPOUIFFMFDUSJDBM
component or the electrical diagram provided with the humidifier
when connecting the power and control wiring inside the
humidifier control cabinet.
t 6TFPOMZBNNTUBOEBSEPS"4$TDSFXESJWFSPO
Vapor-logic
3
control board terminal blocks.
t 6TFBTJOHMFHBVHFNN
2
) pre-tinned wire in each terminal
at the Vapor-logic
3
terminal block. Torque to 4 inch-pounds
(0.4 Nm).
t %POPUUFSNJOBUFNVMUJQMFXJSFTUPBTJOHMF7BQPSMPHJD
3
terminal.
t /FWFSSVOUIFDPOUSPMTZTUFNXJSFTCVOEMFEXJUIPSJOUIFTBNF
conduit as, power wires.
Control cabinet connections
VL3_IOM.pdf 26 11/19/2009 9:11:11 AM