Installation guide

Page 76 • DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual
Information for European models
only
This equipment has been tested by the Canadian Standards
Association International to the Low Voltage, Gas Appliance, and
EMC directives and has been certified by AFNOR for use in all EU
countries.
Authorized countries of destination
The GTS and GTS-DI humidifiers bearing the CE mark are
authorized for use in the European countries listed below.
Austria ...........AT Greece ..........................GR
Belgium...........BE Ireland .........................IE
Switzerland........CH Iceland .........................IS
Germany..........DE Italy ..............................IT
Denmark..........DK Luxembourg ...............LU
Spain .............ES Netherlands ................NL
Finland ...........FI Norway ........................NO
France . . . . . . . . . . . .FR Portugal .......................PT
United Kingdom . . .GB Sweden ........................SE
Appliance category
In relation to the country of destination, this humidifier is classified
under one of the following boiler categories: category I
2H
, I
2L
, I
2E
,
I
2E+
, I
2LL
, I
2ES
, I
2Fi
, I
2ER
, I
3B/P
, I
3P
.
See the unit data plate for the specific category of your appliance.
Electrical warning label
Location: Control cover, shroud
Definition: Electrical shock hazard
Important:
This equipment is for use with second family
(G20, G25) natural gases; and third family
(G30, G31) propane gas. Contact your
distributor before converting to another
group or supply pressure.
Table 76-1:
Gas specifications for European models
Humidifier
model
Volumetric flow rate by gas category
Average flue
temperature
Minimum
draught
requirement
Mass flow rate
of combustion
products
2H-G20-20 mbar
2E-G20-20 mbar
2Es-G20-20 mbar
2L-G25-25 mbar
2LL-G25-20 mbar
2Ei-G25-25 mbar
2E+G20/G25-20/25 mbar
2ER-G20/G25-20/25 mbar
3B-G30-30 mbar
3B-G30-50 mbar
3P-G31-30 mbar
3P-G31-37 mbar
3P-G31-50 mbar
GTS-100 2.31 m
3
/h 2.82 m
3
/h 2.31-2.82 m
3
/h 1.31 m
3
/h 1.49 m
3
/h 121 °C -0.025 mbar 6.9 g/s
GTS-200 4.62 m
3
/h 5.64 m
3
/h 4.62-5.64 m
3
/h 2.62 m
3
/h 2.98 m
3
/h 163 °C -0.025 mbar 13.8 g/s
GTS-300 6.93 m
3
/h 8.46 m
3
/h 6.92-8.46 m
3
/h 3.93 m
3
/h 4.47 m
3
/h 191 °C -0.025 mbar 20.7 g/s
GTS-400 9.24 m
3
/h 11.28 m
3
/h 9.24-11.28 m
3
/h 5.24 m
3
/h 5.96 m
3
/h 218 °C -0.025 mbar 27.6 g/s
GTS-500 11.55 m
3
/h 14.10 m
3
/h 11.55-14.10 m
3
/h 6.55 m
3
/h 7.45 m
3
/h 218 °C -0.025 mbar 34.5 g/s
GTS-600 13.86 m
3
/h 16.92 m
3
/h 13.85-16.92 m
3
/h 7.86 m
3
/h 8.94 m
3
/h 218 °C -0.025 mbar 41.4 g/s
GTS-700 16.17 m
3
/h 19.74 m
3
/h 16.17-19.74 m
3
/h 9.17 m
3
/h 10.43 m
3
/h 218 °C -0.025 mbar 48.3 g/s
GTS-800 18.48 m
3
/h 22.56 m
3
/h 18.47-22.56 m
3
/h 10.48 m
3
/h 11.92 m
3
/h 218 °C -0.025 mbar 55.2 g/s
European models