Safety precautions
• Installation must conform to the requirements of the authority having 
jurisdiction or, in the absence of such requirements, must conform to:
  In the United States: The National Fuel Gas Code, ANSI Z223.1 
(latest edition). 
  In Canada: Local plumbing or waste water codes and other 
applicable codes and with the current code CAN/CGA-B149.1, 
“Installation Code for Natural Gas Burning Appliances and 
Equipment,” or CAN/CGA-B149.2, “Installation Code for Propane 
Burning Appliances and Equipment.” 
  In Europe: The National Gas Safety (Installation & Use) Regulations. 
• Do not install in potentially explosive or flammable atmospheres 
laden with grain dust, sawdust, or similar airborne materials.
• Installation of humidifier in high humidity or salt water atmospheres 
causes accelerated corrosion, reducing the normal life-span of the 
unit.
• To prevent premature heat exchanger failure, do not locate any gas-
fired unit in areas where chlorinated, halogenated, or acid vapors are 
present in the atmosphere.
• Locate the humidifier in an area clear of combustible materials, 
gasoline, and other flammable vapors and liquids.
• With the exception of sealed combustion units, do not locate units 
in tightly sealed rooms or small compartments without provision for 
adequate combustion air and venting. Room air combustion must be 
supplied through a minimum of two permanent openings in the wall, 
with at least one near the bottom. See the table and information on 
Page 30 for additional information.
• Remove all shipping brackets and materials before operating the 
humidifier.
• Do not locate humidifier in a negative pressure space. Combustion 
products could be suctioned from the venting.
• Humidifier flue gases must be vented to the outside atmosphere.
• Power supply disconnect switch must be in the off position while 
making wiring connections to prevent electrical shock and equipment 
damage. All units must be wired in strict accordance with the wiring 
diagrams furnished with this unit.
• Turn off all gas while installing the gas piping and manual shutoff 
valve for the humidifier.
• The appliance and its individual shut-off valve must be disconnected 
from the gas supply piping system during any pressure testing of that 
system at test pressures exceeding 0.5 psig (3.5 kPa).
WARNING!
Overview