Installation guide

DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual • Page 65
Maintenance
mc_052908_0815-2
When the maintenance requirements are complete:
Replace cleanout plate and tighten the nuts on the plate.
Torque the nuts to 25 to 35 in-lb (2.8 to 4.0 N-m).
Verify that the probe rod holder is secure and that the
probe plug and cable assembly are plugged into the probe
rod holder.
Verify that the drain valve assembly is in the closed
position.
Replace and secure all covers and doors.
Turn on the water supply.
Turn on the electrical power.
Turn on gas.
Do not leave humidifier unattended. Allow the humidifier
to cycle through multiple fill cycles and verify that the
humidifier cover, cleanout plate, and probe holder gasket
are not leaking.
3. Off-season maintenance
Perform complete inspection and cleaning of the following:
Probe rods
Skimmer port and water seal
Humidifier tank
Heat exchanger
After cleaning, the humidifier should remain empty until
humidification is required.
GTS standard water models