DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual • Page 59
mc_052708_1555
mc_051408_1430
Both GTS and GTS-DI models
Inspection recommendations:
User inspection every 30 days.
Appliance system inspected once a year by a qualified service
person.
During inspection, verify the following:
Proper field operation of burner. Measure CO, CO
2
%, O
2
%, flue
temperature, and burner efficiency at 100% demand with the
tank at a boil. Verify that measurements are within the guidelines
described in Table 59-1; if not, consult DRI-STEEM.
Flue passageways external to the appliance, such as vent
connector and chimney, are clear and free of obstructions.
Vent connector is in place, sloping upward and is physically
sound without holes or excessive corrosion.
Physical support of the appliance is sound without sagging,
cracks, or gaps between floor stand or tank flanges.
There are no obvious signs of deterioration of the appliance.
Burner flame is blue or orange in color — up to a ¼"
(6 mm) from the surface of the burner.
See “Clean the probes” and “Clean low water cutout probe” on
Page 63 and 64.
Inspecting burner assemblies and heat exchanger tubes
This is not a regular maintenance item, but if the heat exchanger
tubes contain carbon deposits, soot, or other residue, clean as
follows:
Turn off gas, electrical power, and water supply.
Remove gas train shroud.
Disconnect wiring to blowers, flame sensors, gas valves, and
ignition controllers and remove burner assemblies (each assembly
is mounted with four bolts).
Remove vent box.
Use a 6" (150 mm) flue brush with a 24" (600 mm) extension
and reversible drill. Work brush in and out of all combustion
chambers. Note: Disconnecting components from one burner
assembly at a time and then cleaning the corresponding
combustion chamber and burner will ease reassembly.
More on next page
Table 59-1:
GTS products of combustion guidelines
(at 100% demand)
CO
Less than 40 ppm; 0 or low single
digits is typical
CO
2
%
8-10%; 9% is typical for natural gas,
10% is typical for LP gas
O
2
% 4-7%
Flue
temperature
Less than 400 °F plus room temp.
(Less than 204.4 °C plus room temp.)
Burner
efficiency
Greater than 80%
mc_052708_1610
Maintenance
GTS and GTS-DI models