Page 46 • DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual
Rapid-sorb pitch requirements
•  When installing Rapid-sorb with the header outside a horizontal 
airflow duct, consider the following pitch issues:
  – For 1½" (DN40) dispersion tubes, use a fastener of sufficient 
length to accommodate the 1/8"/ft (1%) pitch requirements 
toward the ¾" pipe thread (DN20) header drain fitting.
  – For 2" (DN50) dispersion tubes, the bracket can be mounted 
flush to the ductwork. The 1/8"/ft (1%) pitch typically can be 
accomplished in the length of the hose cuffs used to connect 
the tubes to the header. 
•  See the table below and the drawings on the following pages for 
pitch requirements. 
Table 46-1: 
Pitch of interconnecting piping, dispersion tubes, and headers for Rapid-sorb evaporative dispersion units
Airflow
Type of
interconnecting piping
Diameter of
interconnecting piping
Pitch of
interconnecting piping
Pitch of 
dispersion tubes
Pitch of
header
Horizontal
Vapor hose 1½" (DN40), 2" (DN50)
2"/ft (15%) 
toward
Rapid-sorb
Vertically
plumb
1/8"/ft (1%)
toward
condensate
drain
Tubing or pipe
1½" (DN40), 2" (DN50), 
3" (DN80), 4" (DN100), 
5" (DN125), 6" (DN150)
1/8"/ft (1%)
toward
Rapid-sorb
Vertical
Vapor hose 1½" (DN40), 2" (DN50)
2"/ft (15%)
toward
Rapid-sorb 2"/ft 
toward
header
1/8"/ft (1%)
toward
condensate
drain
Tubing or pipe
1½" (DN40), 2" (DN50), 
3" (DN80), 4" (DN100), 
5" (DN125), 6" (DN150)
1/8"/ft (1%)
toward
Rapid-sorb
Dispersion:
Rapid-sorb
Installation