Installation guide

Page 46 • DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual
Rapid-sorb pitch requirements
When installing Rapid-sorb with the header outside a horizontal
airflow duct, consider the following pitch issues:
For 1½" (DN40) dispersion tubes, use a fastener of sufficient
length to accommodate the 1/8"/ft (1%) pitch requirements
toward the ¾" pipe thread (DN20) header drain fitting.
For 2" (DN50) dispersion tubes, the bracket can be mounted
flush to the ductwork. The 1/8"/ft (1%) pitch typically can be
accomplished in the length of the hose cuffs used to connect
the tubes to the header.
See the table below and the drawings on the following pages for
pitch requirements.
Table 46-1:
Pitch of interconnecting piping, dispersion tubes, and headers for Rapid-sorb evaporative dispersion units
Airflow
Type of
interconnecting piping
Diameter of
interconnecting piping
Pitch of
interconnecting piping
Pitch of
dispersion tubes
Pitch of
header
Horizontal
Vapor hose 1½" (DN40), 2" (DN50)
2"/ft (15%)
toward
Rapid-sorb
Vertically
plumb
1/8"/ft (1%)
toward
condensate
drain
Tubing or pipe
1½" (DN40), 2" (DN50),
3" (DN80), 4" (DN100),
5" (DN125), 6" (DN150)
1/8"/ft (1%)
toward
Rapid-sorb
Vertical
Vapor hose 1½" (DN40), 2" (DN50)
2"/ft (15%)
toward
Rapid-sorb 2"/ft
toward
header
1/8"/ft (1%)
toward
condensate
drain
Tubing or pipe
1½" (DN40), 2" (DN50),
3" (DN80), 4" (DN100),
5" (DN125), 6" (DN150)
1/8"/ft (1%)
toward
Rapid-sorb
Dispersion:
Rapid-sorb
Installation