DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual • Page 45
Installation
General Rapid-sorb installation instructions
•  Before you begin installation, read all dispersion instructions in 
this manual.
•  Before you begin installation, unpack shipment and verify receipt 
of all Rapid-sorb components with packing list. Report any 
shortages to DRI-STEEM factory immediately. The components 
typically include the following:
  – Multiple dispersion tubes
 – Header
  – ¾" × 2" (19 mm × 51 mm) L-bracket
  – A single duct escutcheon plate the size of the header
  – Slip couplings or hose cuffs and clamps. 
  – Accessories such as duct plates, slip couplings, or hose cuffs are 
in a plastic bag. 
  – The bolts and washers for mounting the dispersion tubes to the 
bracket will be in the end of the tubes or packaged in a bag with 
the other accessories. 
  – The tubes, header, and L-bracket are tagged with the customer 
requested identification number written on each component.   
•  When choosing a location for installation, select a location that 
provides necessary access in and around the ductwork or air 
handler.
•  The Rapid-sorb typically is installed centered side to side in a 
duct, or is installed across the face of a coil in an air handler.
•  The center line of the outer dispersion tubes should never be 
closer than 4.5" (114 mm) from the side of the ductwork or air 
handler wall.
•  Rapid-sorbs are provided with an L-bracket for installation:
  – L-brackets that are 50" (1270 mm) or less in length have a hole 
4" (102 mm) in from each end to mount the L-bracket to the 
duct or air handler wall.
  – L-brackets that are greater than 50" (1270 mm) in length have 
an additional hole in the center of the L-bracket. 
 – 
Important: Before marking and drilling holes in the 
duct or air handler, refer to ALL pitch requirements for the 
Rapid-sorb assembly you received (see the table on Page 46). 
The size, quantity, and location of penetrations are determined 
by the specific dimensions and configuration of the Rapid-sorb 
assembly you received. 
 – Note: The hardware for mounting the L-bracket to the duct 
or air handler wall and the hardware for the header support 
bracket is not provided.
•  The Rapid-sorb instructions that follow are for the most 
typical Rapid-sorb installations — installed in a duct horizontal 
airflow with Rapid-sorb header either inside or outside the 
duct. See the Dri-calc Installation Guides library or contact 
your representative/distributor or DRI-STEEM for installation 
instructions for air handler or vertical airflow applications.
CAUTION!
Failure to follow the recommendations in 
this section can result in excessive back 
pressures on the humidifier. This will result 
in unacceptable humidification system 
performance such as leaking gaskets, blown 
water seals, erratic water level control, and 
spitting condensate from the dispersion 
tube(s).
Table 45-1:
Rapid-sorb dispersion tube capacities
Tube capacity Tube diameter
lbs/hr kg/h inches DN
≤ 35 ≤ 16 1½ 40
36-70 17-32 2 50
Table 45-2:
Rapid-sorb header capacities
Header capacity Header diameter
lbs/hr kg/h inches DN
≤ 250 ≤ 113 2 50
251-500 114-227 3 80
501-800 228-363 4 100
Dispersion:
Rapid-sorb