Installation guide
Page 40 • DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual
Installation
•  See the following pages for detailed drawings and notes for 
installing single tube and multiple tube dispersion assemblies.
•  See the hose kit sizing table on this page for single tube 
applications.
Dispersion tube mounting
•  Orient dispersion tube(s) so that tubelets (steam orifices) 
point up.
•  See the table on the next page for dispersion tube pitch 
requirements.
•  When mounting the humidifier above the level of the dispersion 
tube(s), see the drip tee installation drawing on Page 39.
Condensate drain piping
•  Minimum diameter (ID) for draining from one or two dispersion 
tubes: ¾" (DN20) 
•  Minimum diameter (ID) for draining from three or more 
dispersion tubes: 1" (DN25)
•  Condensate drain piping must be rated for 212 °F (100 °C) 
continuous operating temperature.
•  Condensate drain line must be piped as shown in the figures 
on the following pages. Provide a 6" (152 mm) drop prior to a 
5" (127 mm) water seal to:
  − Ensure drainage of condensate from the header
  − Keep steam from blowing out of the drain line
•  After the water seal, run the drain line to an open drain with a 1" 
(25 mm) vertical air gap. Cut the drain line at a 45° angle on the 
end above the drain to permit a direct stream of water into the 
drain pipe while maintaining a 1" (25 mm) air gap. Locate air gap 
only in spaces with adequate temperature and air movement to 
absorb flash steam, or condensing on nearby surfaces may occur.
•  All drain lines must be installed and sized according to governing 
codes.
Table 40-1:
Hose kit sizing by capacity
Maximum 
tube capacity
Hose kit 
(vapor hose, dispersion tube, 
and hardware)
lbs/hr kg/h
28.4 13 1½" (DN40) without drain
56.8 25.8
1½" (DN40) with drain
2" (DN50) without drain
85.2 38.6 2" (DN50) with drain
> 85.2 >38.6
These models require multiple 
tube assemblies and cannot use 
a single hose kit.
Notes:
•  Assemble multiple dispersion tubes or use a 
Rapid-sorb or Ultra-sorb dispersion assembly where 
necessary to accommodate maximum humidifier load.
•  The smallest GTS humidifier steam outlet is 2" 
(DN50). Install an adaptor manifold if using multiple 
1½" (DN40) dispersion tubes.
CAUTION!
Failure to follow the recommendations in 
this section can result in excessive back 
pressures on the humidifier. This will result 
in unacceptable humidification system 
performance such as leaking gaskets, blown 
water seals, erratic water level control, and 
spitting condensate from the dispersion 
tube(s).
Dispersion:
Single tube and multiple tube
Installation