Installation guide

Page 38 • DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual
Threaded pipe nipple
Hose connection
OM-1234
Flange connection
Tubing or pipe
Steam outlet
connection (tubing)
OM-1233
Tubing or hard pipe using hose cuff with clamps
Hose clamps
6"-long (152 mm) hose cuff
Note:
Diameter of interconnecting steam hose, pipe or tubing must be equal to or
greater than the diameter of the steam outlet. Do not use hose, pipe or tubing
that is smaller than the steam outlet.
OM-1231
Steam outlet connection
(threaded pipe nipple)
Pipe unions by
installer
Threaded pipe
Support piping from above
to prevent undue pressure on
humidifier outlet. Allow for
thermal expansion.
Removable spool
piece for service
Vapor hose
Steam outlet
connection (tubing)
OM-1232
Hose clamp
Swing arm by
installer
Steam outlet connection (flange)
Directional arm (up, down, right,
left) by installer
Support piping from
above to prevent undue
pressure on humidifier
outlet. Allow for
thermal expansion.
Support member
Steam outlet connections
Figure 38-1:
Steam outlet connections