Water supply piping general instructions 
The GTS humidifier has a 1" (25 mm) internal air gap to prevent 
back siphoning into a potable water system. However, some 
governing codes may require additional protection such as a 
vacuum breaker or backflow preventer.
The supply water pressure range must be 25 psi to 80 psi (172 kPa 
to 552 kPa). When nonmetallic water piping is used, it must be 
rated to withstand 212 °F (100 °C) or greater temperature. If not, 
the final three feet of piping connected to the humidifier should be 
metallic and should not be insulated.
GTS (standard water) water supply piping
The water supply assembly has a 3/8" pipe thread (DN10) 
connection. Since the primary component of the water supply 
assembly is a solenoid valve, there may be noise issues that surface 
during a fill cycle.
During a fill cycle, the supply water drops the water temperature in 
the tank and may collapse the steam, which can cause a low rolling 
sound. To diminish this, adjust the factory-supplied needle valve 
(installed prior to the fill valve) to decrease the water fill rate, and/
or use hot supply water.
In cases where water hammer occurs when the fill solenoid closes, 
a shock arrester is recommended. Reducing the supply water 
pressure (minimum 25 psi [172 kPa]) or using flexible tubing (rated 
for 212 °F [100 °C] minimum continuous operating temperature) 
may diminish the noise, but installing a shock arrester is the best 
solution. 
The minimum water conductivity for the GTS standard water 
model is 100 μS/cm.