GTS outdoor enclosure sequence of operation
•  Power is applied to the outdoor enclosure.
•  If the ambient temperature in the enclosure is below 
  50 °F (10 °C), the strip heaters are powered up. If the enclosure 
temperature reaches 35 °F (2 °C), power is allowed to the GTS 
subpanel and the GTS unit is enabled. The strip heaters remain 
on until the enclosure reaches 50 °F (10 °C) to ensure that 
the temperature inside the enclosure does not drop below the 
freezing point.
•  When the enclosure temperature is at or above 50 °F (10 °C), the 
GTS tank heats the enclosure. When there is no call for humidity, 
an aquastat maintains tank temperature at the factory default 
of 70 °F (21 °C). This temperature can be reset in the field to be 
from 40-180 °F (4-82 °C).
•  When the ambient temperature in the enclosure reaches 85 °F 
(29 °C), two ventilation fans turn on to cool the electronic 
components. A high limit is also provided to power down the 
GTS if the enclosure temperature reaches 150 °F (66 °C). In a 
high limit situation, the ventilation fans continue to run and once 
the enclosure temperature falls below 130 °F (54 °C), the GTS 
automatically resumes normal operation.
•  A normally open drain valve is provided on the GTS outdoor 
enclosure to drain the tank in the event of a power loss.