Installation guide

Page 8 • DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual
Specifications, capacities, and
weights
Capacity notes
At sea level, approximately 152 Btu are required to raise the
temperature of one pound of water from 60 °F to 212 °F. (At sea
level, approximately 352 kJ are required to raise the temperature
of one kilogram of water from 16 °C to 100 °C.)
• An additional 970 Btu are required to change the state of one pound
of 212 °F water to vapor. (An additional 2257 kJ are required to
change the state of one kilogram of 100 °C water to vapor.)
Another factor to consider is condensation steam loss from
piping. Use the following general steam loss guidelines:
– Vapor hose: 0.15 lbs/hr/ft
(0.22 kg/h/m)
Insulated pipe: 0.05 lbs/hr/ft (0.07 kg/h/m)
Hard pipe and dispersion tubes: 0.50 lbs/hr/ft (0.7 kg/h/m)
High-eciency dispersion tubes: 0.20 lbs/hr/ (0.298 kg/h/m)
For more detailed information about condensation steam loss, see
the DRI-STEEM Design Guide or our software program, Dri-calc.
LP gas
All models operate at rated
input.
High altitude
An input derate exists when operating units at a high altitude. See
Table 8-2 for high altitude derate information.
* GTS-400 models are derated 10% from 2001-4500 ft in Canada.
Table 8-1:
GTS specifications, capacities, and weights for North American models only
GTS
model
Maximum
steam
capacity
Input
Water usage
at maximum
capacity**
Tank
volume
GTS GTS with outdoor enclosure
Full load
amps*
Operating
weight
Shipping
weight
Operating
weight
Shipping
weight
lbs/hr kg/h MBh kW m
3
/h
gals/
hr
litres/
hr
gals litres lbs kg lbs kg lbs kg lbs kg
120 V
60 Hz
230 V
50 Hz
GTS-100 75 34 100 29 2.76 9 34.1 48 181.7 700 320 375 170 800 365 500 230 1.8 2.8
GTS-200 150 68 200 59 5.52 18 68.1 48 181.7 700 320 375 170 800 365 500 230 1.8 2.8
GTS-300 225 102 300 88 8.28 27 102.2 52 196.8 850 385 450 205 1000 455 600 270 3.0 4.0
GTS-400 300 136 400 117 11.04 36 136.3 52 196.8 850 385 450 205 1000 455 600 270 3.0 4.0
GTS-500 375 170 500 147 13.80 45 170.3 76 287.7 1100 500 600 270 1450 660 950 430 4.5 5.5
GTS-600 450 204 600 176 16.56 54 204.4 76 287.7 1100 500 600 270 1450 660 950 430 4.5 5.5
GTS-700 525 238 700 205 19.32 63 238.5 89 336.9 1400 635 700 320 1750 795 1050 475 6.0 7.0
GTS-800 600 272 800 234 22.08 72 272.5 89 336.9 1400 635 700 320 1750 795 1050 475 6.0 7. 0
* Add 15 full load amps for outdoor enclosure heater load on all GTS models, add 1 full load amp for an outdoor enclosure without heaters.
** Add 10% to account for skim and automatic drain/flush features if utilized (standard water units only).
Table 8-2:
High altitude derate
Altitude
Input
derate %
feet meters
0–2000 0–610 0
2001–2500 610–765 2*
2501–3000 765–915 4*
3001–3500 915–1065 6*
3501–4000 1065–1220 8*
4001–4500 1220–1370 10
4501–5000 1370–1525 12
5001–5500 1525–1675 14
5501–6000 1675–1830 16
6001–6500 1830–1980 18
6501–7000 1980–2135 20
7001–7500 2135–2285 22
7501–8000 2285–2440 24
Important: See Pages 76-77 for
additional European model specifications
and capacity notes.