Technical data

SHR 521 20
© Drayton 06334 SHR 521 20.monen.indd
17 |
1 2
S1 S2 S3
3 4 5 6
Temp. Sensor
Pt1000
LNR1NR2N
201918171615
S4
7 8
141312
2 (1) A (220 ... 240)
V~
2 (1) A (220 ... 240) V~
R1
R2
T4A
220 ... 240
V~
5. Tips for fault finding
can fuse T4A
If a malfunction occurs, a notification is given on the display
of the controller:
Operating control lamp
Warning symbol
Operating control lamp off
The power supply to the controller should
be checked if the control lamp goes out.
o.k.no
The can fuse of the controller is defective.
It can be replaced after removal of the
front cover (spare fuse is enclosed in the
accessory bag).
Operating control lamp ashes red. On the display the
symbol and the symbol appear.
Sensor defect. An error code is shown
on the relevant sensor mode instead of
a temperature.
- 88.8888.8
open circuit. Check
the line.
Short-circuit.
Check the cables.
Pt1000 temperature sensors when discon-
nected can be checked with an ohmmeter.
In the following the resistance values
corresponding to different temperatures
are listed.
Resistance values of
the Pt1000-sensors