Installation Guide

3
Important Safeguards and Warnings
WARNING: Shock and fire hazard
If the Heat Cable System is damaged or not installed properly, fire or shock could occur resulting in serious
personal injuries or damage to property. You must carefully follow the warnings and instructions contained
in this manual.
· A qualified thermostat must be used.
· It is important that this equipment is installed only by qualified electricians who are familiar with the proper
sizing, installation, construction and operation of floor warming system and the hazards involved. The
installation must comply with all national and local electrical codes. If you are unfamiliar with these
requirements, contact an electrician.
· The heating cable is designed for under floor heating purposes only. Be sure that the floor is not penetrated
by nails, screws, or similar devices that can cause damage on first installation or during subsequent floor
repairs in the future.
· If the Heat Cable System is damaged, it must be replaced. Do not attempt to splice or repair any part of the
system
1 General Information
1.1 Use of the Manual
This manual describes the Heat Cable floor heating system how to design the room, select the product,
and install the system. It is important to thoroughly review this manual and the following document prior to
installation.
Dr. Heater Thermostat Installation and Operation Manual
1.2 Safety Guidelines
The safety and reliability of any floor heating system depends on proper design, installation, and testing.
Incorrect installation or mishandling of the product can cause damage to the heating cable, system
components and property, and can create a risk of fire or shock. The guidelines and instructions contained in
this guide are important. Follow them carefully to minimize these risks and to ensure that the Heat Cable
system performs reliably.
Pay special attention to the following:
·Instructions marked Important
·Safety warnings identified as WARNING
1.3 Remember to measure resistance
The resistance should be measured between the two conductors, white and black. Compare this resistance
reading to the resistance specified in the Product Selection “Table 1 or Table 2”. The value should be within
±10%.
Also, measure the resistance between the white, black and shielding/ground wire. Both should read infinity.
Please refer to “5 Commissioningfor instructions on how to measure the resistance.
Important: measure the resistance four times during the installation process
Remember to always measure, verify and record the actual resistance throughout the installation
process (out of the box, after installation, after thin set cement or self-leveler application and after
installation of floor tiles).
1.4 25-year Limited Warranty
For a period of twenty-five (25) years from the date of purchase Dr. Heater warrants that the heating cable
is free from defects in material, design and workmanship. The warranty is only valid if the warranty
certificate has been properly completed and mailed, and the installation is in accordance with the
installation instructions.