Use and Care Manual
5
WARNING: All wiring must be installed by a certified/licensed
electrician.
The heater must be grounded in accordance with applicable national
and local building codes.
WARNING: To reduce the risk of fire, do not store or use gasoline or
other flammable vapors and liquids in the vicinity of the heater.
All wiring procedures and connections should be in accordance
with applicable national and local codes.
NOTE: Compatible with a 240V Line Voltage Double Pole Wall
Thermostat. Must be installed by a certified/licensed electrician.
Before installation:
Disconnect the main supply connection.
Supply cables should be 8 AWG (8.3 mm
2
) copper wires.
The heater must be connected to an individual branch circuit
protected by a 40 Amp circuit breaker only.
Supply cables must be equipped with a dual pole circuit breaker
rating at least 240V 40A/pole as main cutoff switch of power
connection to the heater.
CAUTION: HIGH TEMPERATURE, RISK OF FIRE. Keep electrical
cords, drapery, furnishings, and other combustibles at least 3 feet
(0.9 m) from the front of the heater and away from the sides and rear.
WARNING: To reduce the risk of fire, do not store or use gasoline
or other flammable vapors and liquids in the vicinity of the heater.
INSTALLATION INSTRUCTIONS:
1. This heater should be installed at least 6 feet (in the United States)
or 2.4 meters (in Canada) from the floor and no closer than 1 foot
(0.3 m) from any adjacent surfaces or walls. This minimum distance
must be maintained.
2. Do not install closer than 1 foot (0.3 m) from any adjacent surfaces
INSTALLATION INSTRUCTIONS