WARNING: All wiring must be installed by a certified/licensed
electrician. The heater must be grounded in accordance with
applicable national and local building codes.
WARNING: To reduce the risk of fire, do not store or use gasoline
or other flammable vapors and liquids in the vicinity of the heater.
All wiring procedures and connections should be in
accordance with applicable national and local codes.
NOTE: Compatible with a 240V Line Voltage Double Pole Wall
Thermostat. Must be installed by a certified/licensed electrician.
Before installation:
Disconnect the main supply connection.
Supply cables should be 6 AWG (13.3 mm
2
) copper wires.
The heater must be connected to an individual branch circuit
protected by a 60 Amp circuit breaker only.
Supply cables must be equipped with a dual pole circuit breaker
rating at least 240V 60A/pole as main cutoff switch of power
connection to the heater.
Wiring compartment for accommodating supply cables and pigtail
leads are adequate and measured free space of 2524.67 cm
3
.
Tools/ Materials Needed (Not Included):
·Regular Screwdriver Set
Unpacking Contents
·
Heater
·Owner's Manual
·
Warranty Card
·Heater Handle
INSTALLATION INSTRUCTIONS