User manual

82
DPMS XPQ User Manual
Fig 4.16 Alarm Log
SOE Function
There are 4 DI inputs, it can record changing information of DIs. The time
resolution is 1ms. It can also determine whether to enable waveform capture
and which kind of triggering by setting “DI triggering waveform capture mode” in
system parameters. Its register forms a 16-bit unsigned integer. Bit1,bit0=DI1;
Bit3,bit2=DI2;Bit5,bit4=DI3; Bit7,bit6=DI4. “00” stands for none, “01” stands for
from OFF to ON, “10” stands for from ON to OFF ,“11” stands for trigger at any
change.
Format: DI status | occur time yyyy |mm | dd | hh | mm | ss | ms
There are 20 groups of records, it will begin with the rst one after power