no output. The CT primary value of I1 is 200A. The primary voltage of U1 is
10000V, PT2 is 100V. Then let’s look how all the related registers are set.
The rst record:
According to the table, the serial number of I1 is 9 ((14d8H)= 9); Conditions
in equation 1 determine the high limit. So “comparison mode” (14d9H) = 1(>).
CT1 is 200A, according to the relationship between the communication value
and numerical value. I=Rx X(CT1/5)/1000, so I1 is 180A. Then the limit is (14daH)
= 4500; Delay 5s, as the unit of Limit_t register is 10ms, so the delay time is
(14dbH) = 500; Alarming but no waveform triggering, “waveform capture” (14dcH)
= 0.
The second record:
According to the table, the serial number of U1 is 1 ((14ddH) = 1);
Conditions in equation 1 determine the low limit. So “comparison mode” (14d9H)
= 3(<); PT1 is 10000V, according to the relationship between the communication
value and numerical value, U=Rx X (PT1 / PT2) /10, so the register value should
be 998; Delay 10s, as the unit of Limit_t register is 10ms, so the delay time is
(14e0H) = 1000; Alarming but no waveform triggering, so “waveform capture
(14e1H) = 0.
Settings between the two records:
“Alarming output” of the 1st, 2nd(101fH) = 0x0003; No hardware output,
(1020H)=0; (1021H)=0;(1022H)=0; (1023H)=0; logical and(1024H)=0x0001; At
last, the” alarming enable”, (101dH) =1.