User manual
76
DPMS XPQ User Manual
“Delay time” indicates the time period that the event keeps happening after
the setting equation or in equation is satisfied, which is used to confirm the
event. Its value ranges from 0 - 6000 (integer) with a unit of 10ms. There is no
delay when it is set to be 0, so the event triggers alarming at once. For example,
if it is set to be 20, delay is 20*10=200ms. “Waveform triggering” refers to
whether waveform capture works when the set event occurs.
address parameter range
14F0H First group: serial number 0~246
14F1H First group: comparison mode 1:more,2:equal,3:less
14F2H First group: setting value Related with parameters
14F3H First group: delay time 0~6000(*10ms)
14F4H First group: waveform capture 1:capture; 0:not capture
Table 4-1 rst group of alarming settings
Serial number parameter
0~32 33 basic analog measurements parameters from“Frequency” to
“Loadcharacteristic” discussed in chapter 5.
33~241 209 parameters from “THD_V1” to “K Factor of I3” discussed in chapter 5.
242 Consumption energy predict demand
243 Generation energy predict demand
244 Consumption reactive energy predict demand
245 Generation reactive energy predict demand
246 Apparent energy predict demand
Table 4-2 parameters for alarming
Thus far, the equations or in equations are nished, but the setting are not
nished yet, we have to go through the following steps to nish them.