User manual

47
POWER INSTRUMENTS
reactive energy and generation of reactive energy
respectively.
10: The same as DO1 for setting, and they don’t affect
each other.
11: The DO pulse width is an integer from 1 - 50. One
digit is 20ms.
12: Pulse rate means the energy value per pulse. It
can be an integer of 1 - 6000. One digit is 0.1kWh or
0.1kVarh.
13: For the latching mode, the relay can be used to
output two states: on or off. For the momentary mode,
the output of the relay changes from off to on for a
period of time, Ton and than goes off. Ton can be set
from 50-300ms. (0: latching; 1: momentary).
14: When the relay mode is set to momentary, the
closing time, Ton is an integer from 50 - 3000ms.
15: The same as Relay1.
16: The same as Relay1 and they dont affect each
other.
17: The “on” time can be set from 0 - 120 minutes. The
back light will always be “on” if the setting value is 0. If
it is another value, it means after a long time it goes off
if no key has been pressed. It will be “on” whenever you
10 : 09 : DO2 output item
11:The D O pulse width
12 : Energy pulse rate
08: DO mode setting
09 : DO1 output item
V/A
V/A
V/A
V/A
V/A
13 : Relay 1 mode
14 : Relay 1 closing ti m e
V/A
V/A