01: It is any digit from 1 - 247.
02: 1200, 2400, 4800, 9600, 19200, 38400bps are
available.
03: Voltage input could be one of three modes, 3LN,
2LN and 2LL. (Refer to chapter 2)
04: could be one of the three modes, 3CT, 2CT and 1CT.
(Refer to chapter 2)
05: PT1 value is an integer from 50.0 - 500000.0, the
unit is volt.
06: PT2 value is an integer from 100 - 400. The unit is
volt. If there is no PT on the voltage input side of meter,
the PT1 and PT2 should be the same and equal to the
input rated voltage.
07: CT1 value is an integer from 5 - 50000 for a 5 Amp
rated current meter, and 1 - 50000 for a 1 Amp rated
current meter.
08: Output mode of DO can be set as alarm (AL) and
pulse (PLS).
09: It is an integer from 0 - 4 and stands for no output,
consumption energy, generation energy, absorption