User manual

36
DPMS XPQ User Manual
Recommendations for high quality communication:
 
Good quality shielded twisted pair of AWG22 (0.6mm2) or larger is very
important.
 
The shield of each segment of the RS485 cable must be connected to
the ground at one end only.
 
Keep communication cables as far away as possible from sources of
electrical noise.
 
Use an RS232/RS485 or USB/RS485 converter with optical isolated
output and surge protection.