User manual

32
DPMS XPQ User Manual
There are two mode selections for relay output, one is latching, and the
other is momentary. For the latching mode, the relay can be used to output two
states, on or off. For the momentary mode, the output of the relay changes from
off to on for a period of time Ton and then goes off. Ton can be set from 50-
3000ms.
The wire for relay output should be between AWG22 (0.5mm
2
)~AWG16
(1.3mm
2
).
Digital Output (DO)
There are two digital outputs as an option. The terminals of the digital
output are DO1+, DO1-(35, 36) and DO2+, DO2-(37, 38). These two digital
outputs can be used as an energy pulse output or over limit alarming output.
The digital output circuit form is Photo-MOS. The simplied circuit is in g 2.30.
Fig 2.30 Digital output Circuit
The Max output voltage and current are 100V and 50mA.
When the digital output is used as pulse output, DO1 and DO2 can be
Fig 2.30 Digital output Circuit
Power
Supply
Acuvim-X
Photo -Mos