User manual
110
DPMS XPQ User Manual
Alarming Records
There are 16 groups of records with the same format. Function code: 03H
for Reading, 10H for writing. Please refer to chapter 4 for more details.
Address Parameter Range Format code
1540H First group: alarming status 0~65536 F1
1541H Fi r s t g r o u p : p a r a me t e r
number
0~246 F1
1542H First group: over range or
reset value
Related with parameters F7~F21
1543H~1549H First group:
occur time: yyyy:mm:dd
time F3
154AH~15DF 2ed to 16th group Same as the rst group
SOE
There are 20 groups of records with the same format. Function code: 03H
for Reading, 10H for writing. Please refer to chapter 4 for more details.
Address Parameter Range Format code
15E0H First group: DI status 0~16 F1
15E1H~15E7H First group: occur time:
yyyy:mm:dd:hh:mm:ss
time F3
15E8H~167FH 2ed to 20th group Same as the rst group
Waveform Record
There are 5 groups of records including capture time, trigger condition
and waveform data with the same format. The relationship between voltage
waveform data and the numerical value is: numerical value (V) = waveform
data*0.2525. The relationship between current waveform data and the numerical
value is: numerical value (A)= waveform data*0.003071. Waveform data are
secondary values of PT or CT.