User manual
109
POWER INSTRUMENTS
TOU of Current Month
TOU of current month is stored here. It refreshes every second and clears
at the balance time. Function code: 03H for Reading, 10H for writing.
Address Parameter Range Format code
142AH~14BBH the same as the accumulating TOU table in series
Three phase consumption energy (all), three phase generation (all), three
phase absorption reactive (all), three phase generation reactive (all) and three
phase consumption, three phase generation, three phase absorption reactive
, three phase generation reactive are the same physically, but their data may
differ because they are controlled by different clearances. The former is cleared
at the TOU clearance time while the latter is cleared at the real time clearance
time. Furthermore, if the TOU function is disabling, the former will cease without
any effect of the latter.
Event Alarming Setting
There are 16 groups of records with the same format. Function code: 03H
for Reading, 10H for writing. Please refer to chapter 4 for more details.
Address Parameter Range Format code
14F0H First group: serial number 0~246 F1
14F1H First group: comparison
mode
1:more,2:equal,3:less F1
14F2H First group: setting value Related with parameters F7~F21
14F3H First group: delay 0~6000(*10ms) F1
14F4H Fir s t g rou p: w ave for m
capture
1:capture,
0:not capture
F1
14F5H~153FH 2ed to 16th group Same as the rst group