Owner`s manual
01-01 Page 6 29863C
DV450S DIRECT VENT ROOM HEATER
28"
27 - 3/8"
30 - 3/8"
16 - 3/4"
19 - 1/8"
22 - 5/8"
8"
5 - 1/8"
39"
DV450S Front View - With and Without Optional Warming Shelves
DV450S - With Optional Blower
DIMENSIONS
Figure 1
Minimum Clearances To Combustibles
The following clearances to combustibles must be main-
tained:
Minimum clearances to the floor - 0"
Back of unit to wall - 6”
Sides of unit to wall - 9"
Base of the unit to ceiling - 72".
Minimum clearances to Venting are as follows:
Horizontal runs require a 1-1/2” minimum Air Space on the top and
an 1/2” minimum Air Space on the sides and bottom of the outer
Vent Section. If an Elbow is being used,in an enclosed wall, floor
or ceiling, a top Air Space clearance of 3” must be maintained.
Vertical rise sections require a 1” minimum Air Space completely
around the Vent section. These clearances must be maintained
at all times.
This appliance is certified for installation in a bed/sitting sitting room
in the U.S. and Canada.
Mobile Home Installations. Appliances installed in Mobile Homes
must be secured to the floor in a minimum of two locations.
STOVE
STOVE
6"
9"
6"
9"
48"
MAX.
4"
4"
STOVE
HEARTH PROTECTION IS NOT
NECESSARY WITH THIS APPLIANCE
ON A HARD SURFACE.
Positioning the Appliance.
This appliance may be placed on a combustible or non-combus-
tible continuous, flat surface. When the appliance is installed
directly on carpeting, tile or other combustible material other than
wood flooring, the appliance shall be installed on a metal or wood
panel extending the full width and depth of the appliance. Slide
the Heater into position and level the Heater from side-to-side
and front-to-back. Shim as necessary.
CLEARANCES