Sense Control Installation & User Instructions

Table Of Contents
Appendix 3: Distance from combustible material
Sense 100/103/113/200/203 4.9 kW - 7 kW - Minimum distances in mil-
limetres for version without heat shield
1
2
100
100
100
300
750
150
150
100
100
1000
700
840
900
900
750 530
650
750
100
300
100
100
500
300
300
09-20021-021
1 Combustible material
2 Incombustible material, thickness 100 mm
Please note: In order to guarantee the supply of combustion air when there is no outside air supply con-
nection, the distance from the connection collar for the outside air to the wall must be at least 20 mm. If
necessary, the connection collar can be removed.
34
Subject to change because of technical improvements