Operating Instructions and Installation Instructions
2300 - 2400  35  03.27865.100 
Convection chamber: 
The convection chamber topside must be airtight. For that purpose, you can use a 
cover of steel, concrete, or any other fire-resistant material, and put extra insulation 
on top of it. Make sure that the cover is well horizontally placed.  
The  cover  must  be  installed  at  30  cm  at  least  above the  smoke  dome. The  outlet 
grids (optional) must be installed straight under that cover. Make sure that convec-
tion outlet area is big enough: minimum 500 cm². 
In the convection chamber no combustible material must be used. Make sure that, 
when  using  other  auxiliary  material  such  as  steel,  it  will  not  function  as  a  heat 
bridge. 
The picture on the next page shows an example of fireplace installation within com-
bustible material. 
3.4.  Finishing 
When the appliance is installed in the  right place,  its connection with the chimney 
made airtight, and the masonry mantle completely mounted, all loose parts are in-
stalled in the appliance. 
Your fireplace is now ready to be used.  
Depending on the materials used for mounting, it is recommended to wait for some 
time until all masonry is dry before lighting a fire. 
Attention: never light a fire with the inner plates or refractory stones removed. 
3.5.   Packaging materials 
Packaging materials should be disposed of in a responsible way and in accordance 
with governmental regulations. 