2. DESIGN FEATURES
1. INSTALLATION INSTRUCTIONS
Figure 2.1 shows the Intelligent Fixture Sensor on the left and the Intelligent Fixture Controller on the right. Salient
features are highlighted for each device.
Retention Ring
Housing
Push-in
Terminals
Push-in
Terminals
Retention Ring
LED Indicator
& Reset Button
Bezel
Fits Standard
1/2 inch
Knockout
Occupancy and
Daylight Sensor
BT-IFC-ABT-IFS-A
3. SPECIFICATIONS
PART NUMBER • BT-IFS-A • BT-IFC-A
NAME • Intelligent Fixture Sensor • Intelligent Fixture Controller
FUNCTIONALITY
• 0-10V Dimming with DIM-to-OFF (LED Driver dependent)
• Occupancy, Vacancy, Partial ON, & Partial OFF
• Adjustable Occupancy Timeout: 5 to 90 minutes
• Primary & Secondary Daylight Harvesting (CLC)
• Bluetooth beacon for digital ceiling, IoT, and location services
strategies
• Download Douglas Lighting Controls BTCC APP from the
Apple App store for commissioning
• 0-10V Dimming with DIM-to-OFF (LED Driver dependent)
• Listed for emergency lighting control when used on a
dedicated emergency power bus
• Occupancy and daylighting control features as shown at
left when networked with one or more BT-IFS-A sensors
• Bluetooth beacon for digital ceiling, IoT, and location
services strategies
• Download Douglas Lighting Controls BTCC APP from the
Apple App store for commissioning
OCC. SENSOR
MOUNTING HEIGHT
• Up to 16.4ft (5m) • Not applicable
WIRING • Use #20 to #26 AWG solid copper conductors stripped to 4mm
INPUT VOLTAGE • 12VDC – 26.5VDC; Power draw: 0.6W maximum, 0.25W typical
WIRELESS RANGE
• 150ft Clear line of sight, 50ft through standard walls
• Distances may vary based on location and environment
• Additional devices may be required at time of commissioning to ensure Bluetooth network integrity
NOTIFICATIONS • LED indicator for commissioning and occupancy (IFS)
ENVIRONMENT
• Indoor, stationary, non-vibrating, non-corrosive atmosphere, and non-condensing humidity
• Suitable for Use in Other Environmental Air Space (Plenums) in Accordance with Section 300.22, (C) of the National Electrical
Code.
• Operating temperature: 32°F to 131°F (0°C to 55°C)
• Storage temperature: -40°F to 140°F (-40°C to 60°C)
DIMMING
• Two 0-10V dimming channels, each capable of sinking up to 25mA
• Typical use is with single channel 0-10V LED drivers providing auxiliary output power and DIM-to-OFF capability
• May also be used with dual-channel, tunable white LED drivers providing auxiliary output power and DIM-to-OFF capability
CERTIFICATIONS
• UL916, UL2043 (Plenum)
• May be installed through a knockout in the luminaire wiring enclosure or installed external to the enclosure and powered with a
Class 2 circuit using Class 2 wiring methods
WARRANTY • Standard 5-year warranty