Product Overview
Straight Length BTU/hr. NATURAL GAS, 0.64 SG, 1000 BTU/cu.ft., 0.5"w.c. pressure drop
CONFIGURATION
NOMINAL LENGTH
SERIES Nominal ID 14" 18" 24" 30" 36" 48" 60" 72"
in
30, 30C, 31
1
⁄
2
174,500 164,200 150,000 136,000 125,000 106,000 93,200
86,000
40, 40C, 41
3
⁄
4
338,500 318,500 290,900 270,500 255,900 217,000 187,400
173,900
50, 51 1 667,500 637,000 581,800 545,200 515,900 442,700 398,900
347,800
60, 61 1-
1
⁄
4
1,171,500 1,139,000 1,075,000 1,010,500 946,000 817,500 725,500
634,000
Straight Length BTU/hr. LP GAS, 1.55 SG, 2500 BTU/cu.ft., 0.5" w.c. pressure drop
CONFIGURATION
NOMINAL LENGTH
SERIES Nominal ID 14" 18" 24" 30" 36" 48" 60" 72"
in
30, 30C, 31
1
⁄
2
279,200 262,720 240,000 217,600 200,000 169,600 149,120
137,600
40, 40C, 41
3
⁄
4
541,600 509,600 465,440 432,800 409,440 344,000 315,840
278,240
50, 51 1 1,068,000 1,019,200 930,880 872,320 825,440 708,320 638,240
556,480
60, 61 1-
1
⁄
4
1,874,400 1,822,400 1,720,000 1,616,800 1,513,600 1,308,000 1,160,800
1,014,400
Minimum Flow Capacity
NOTICE
The minimum flow capacity values in the charts are at 0.5" w.c. pressure drop
(inlet pressure minus outlet pressure). If your gas system has more available
pressure drop then a general rule of thumb approximate calculation is as
follows:
Minimum Flow Capacity @ your pressure drop = Square Root
(your pressure drop/0.5) x value from chart
Example: What is the approximate minimum flow capacity
(natural gas) of the Dormont 30 Series x 24" @
1" wc pressure drop?
Answer: Square Root (1/0.5) x 150,000 = 212,132 BTU/hr
WARNING
All installations must completely comply with all Dormont
manufacturing company warnings and instructions, national,
state and local codes and all applicable ANSI standards.
ES-D-GAC_Generators 1740 © 2017 Dormont
USA: T: (800) 367-6668 • F: (724) 733-4808 • Dormont.com
Canada: T: (905) 332-4090 • F: (905) 332-7068 • Dormont.ca
Latin America: T: (52) 81-1001-8600 • Dormont.com
The information contained herein is not intended to replace the
full product installation and safety information available or the
experience of a trained product installer. You are required to
thoroughly read all installation instructions and product safety
information before beginning the installation of this product.
NOTICE