5.7.6.3 Switching the external DC power supply to OUT1
By setting the jumper pair with designation VREL, a DC power supply connected via
the VREL terminal (max. 30 V DC, 2 A) is switched to the OUT1 output.
This variant can be used both with device power supply via PoE and device power
supply via an external 24 V DC power supply unit.
Principle of output wiring Jumper position
IMPORTANT: Only the jumper
pair VREL may be set. All other
jumpers may not be set.
5.7.6.4 Switching 24 V DC to OUT1
By setting the jumper pair with designation 24 V DC, the 24 V DC power supply (ter-
minal 24 V EXT) is switched to the OUT1 output. Consumers, for example door open-
ers which are operated with 24 V DC, can be directly connected to OUT1 in this way.
This variant can be used only with device power supply via an external 24 V DC
power supply unit. Not for power supply via PoE.
Principle of output wiring Jumper position
IMPORTANT: Only the jumper
pair 24 V DC may be set. All
other jumpers may not be set.
5.7.6.5 Connecting door openers
Closed-circuit door-openers and open-circuit door-openers can be used.