Specifications

9
Installation, Operation and Maintenance Manual
PowerCore
®
Dust Collectors – Series CPV
Mounting over aperture
1 Check that the aperture and fixing holes are correct in size and position to
suit the mounting-flanges of the PowerCore dust collector (details of aperture
and mounting flange fixing positions are provided in Publication 3010).
2 Open the access door and remove the pack of
sealing strip from the clean air chamber.
Apply two continuous beads of sealing strip all round
aperture, on either side of the fixing holes, as shown.
3 Following the general guidance to lifting, lift and position the collector until
the mounting-flange is seated in position over the aperture. Match up fixing-
holes, install bolts, washers and nuts and tighten down all round to form an
airtight seal.
Fixing bolts etc. are not supplied by Donaldson.
Compressed air requirements
PowerCore dust collectors require an independent supply of clean, dry, oil-free
compressed air. Details of atmospheric pressure and quantity are given in
Table 3 (refer to ‘Specification’ section). A design label is also attached to each
manifold. Where an existing factory mains system is to be used it may be
necessary to install an additional moisture separator in the supply line to the
collector. If a compressor is being installed to supply the collector, then the
following conditions should be observed as far as possible:
Type of compressor
Use a compressor of ample capacity an overloaded compressor tends to
produce excessively contaminated, moisture-laden air.
Location of air intake
Avoid locating the air intake in an excessively polluted area and install an adequate
air intake filter. The compressor air intake should be sited, if possible, on the
north side of the building – fresh air drawn from the north side is usually cooler
and denser, and therefore has a lower moisture content. (South of the equator
the reverse will apply).
Layout and installation of air lines
The pipework between compressor and dust collector should be long enough to
act as a cooling device for the compressed air. A typical requirement for the
smaller installation would be 10m (30ft) of 12mm (½" NB) piping. For further
details see Table 3. The piping should be installed to provide a fall in the direction
of air flow to assist in the drainage of accumulated moisture. A moisture separator
should be provided at the lowest point of the installation.
INSTALLATION