User manual
EN
SinePower Using the inverter
15
9.3 Switching to energy-saving mode
I
➤ With the inverter off, push the remote control‘s on/off button (fig. 3 1) for 5 s to
activate or deactivate the save mode.
✓ The remote control‘s status LED (fig. 3 2) flashes six times.
✓ After that, the remote control‘s status LED (fig. 3 2) indicates the operation
mode:
– Constantly lit: Normal mode activated
– Flashes: Energy-saving mode activated
9.4 Configuring the net configuration
D
Using the dip switch you can define in which net configuration the inverter shall
operate.
NOTE
The inverter automatically switches to normal mode when a load with
more than 45 W is connected.
DANGER!
Changing the net configuration results in risk of lethal injury.
The dip switch must only be set by qualified personnel.
Remove the the dip switch‘s protection cap for configuring only. Insert
the protection cap to prevent switching the dip switch‘s setting.
Parameter Dip switch
TN grid
An external downstream circuit breaker (RCD) is
necessary.
On
IT grid
Operation with one load only or installation of an
external insulation monitor.
National standards shall apply!
Off