Using the inverter SinePower
14
After the self-test is completed successfully, the status LED (fig. 2 2) indicates
the operation mode:
Constantly lit: Normal mode activated
Flashes four times: Energy-saving mode activated
9.2 Status indications
The LED (fig. 2 2) shows the operating condition of the inverter.
The inverter switches off if:
The battery voltage drops below 10 V (12 Vg connection) or
20 V (24 Vg connection).
The battery voltage exceeds 16 V (12 Vg connection) or
32 V (24 Vg connection).
The inverter is overloaded.
The inverter overheats.
In case of shutdown due to overvoltage or undervoltage the inverter restarts when
the set voltage value is reached.
In case of shutdown due to overload or overheating proceed as follows:
Shut down the inverter with the main switch (fig. 2 1).
Check that the inverter is sufficiently ventilated and that the ventilation grilles are
unimpeded.
Wait 5 – 10 minutes and switch the inverter on again without any electric
consumers.
Display Input voltage
Constantly lit Normal mode
Long flash, short interruption Inverter overheated/Overload
Quick flash Overvoltage/Undervoltage
Off Other fault