SinePower Connecting the inverter
19
9.5 Connect multiple appliances
The device is equipped at delivery with galvanic isolation. For the safe operation of
multiple appliances, it is essential that a circuit breaker (residual current circuit
breaker) is built into the socket distribution circuit, see sample circuit diagram in
fig. 6, page 5.
Sample circuit diagram legend:
!
Install a residual current circuit breaker in the socket distribution circuit.
9.6 Setting the earthing bridge (fig. 5 5, page 4)
Remove the earthing screw from the bottom hole.
Screw the screw into the top hole.
No. in
fig. 6,
page 5
Explanation
1 230 Vw power source
2 additional devices, e.g. battery charger, refrigerator
3 DC power source (battery)
4Inverter
5 Set grounding bridge (At delivery: not set, shown by dotted line)
6 Circuit breaker (residual current circuit breaker)
7 Socket distribution circuit for appliances
WARNING! Danger of electrocution!
If you wish to connect more than one appliance to the inverter and install
a socket distribution circuit, you must arrange a circuit breaker (residual
current circuit breaker) and set a grounding bridge in the inverter.