Specifications

© 2015 Digital Monitoring Products
SCS-104 Dialer
Dialer Line Enable: Select to enable Dialer Lines 1-4 on each card number.
Send ANI/DNIS Information: Select to enable the Automatic Number Identification (ANI) and Dialed
Number Identification Service (DNIS) information to be sent. ANI sends the phone number that the
panel is using to call. DNIS sends information about the phone number the panel dialed.
Send Caller ID Information: Select to enable the Caller ID information to be sent to host automation.
Echo Cancel Disable: Echo Cancellation is technology used by telephone companies to eliminate echo
from voice telephone transmissions. In some cases this technology can interfere with alarm signals. If
you have problems with Echo Cancellation interfering with your signals, select to turn off the echo
cancellers. If you are not having problems with the telephone company echo cancellation, do not select
to leave the echo cancelers on.
SCS-104 Network
Network Line Enable: Select to enable the network for the selected line card. Default is selected.
Local IP Address: Enter the SCS-104 IP address. This address must be unique and cannot be
duplicated. The default value is 192.168.000.250.
Local Port: This identifies the port used to communicate messages to and from the panel. If a setting
change is required, enter the new number. Valid range is 1 to 65,535. The default value is 2001.