Specifications
© 2015 Digital Monitoring Products
Receiver Key: The Receiver Key is a number that the receiver uses as a password to confirm its
identity to panels. Enter the number that you will use as a key to identify the receiver in the Receiver
Key field.
If the key numbers programmed into the panel and the receiver match, the receiver and the panel will
communicate. If the numbers do not match, you will see the "Invalid receiver number" error message,
and the panel and the receiver will not be able to communicate.
Once you enter the Receiver Key, it is important that you write it down on the SCS-1 or SCS-1R System
Configuration Record Sheet provided in the Remote Link User Guide appendix, and store it in a safe
place.
System > Configure > SCS-1 Line
Select System > Configure > SCS-1 Line to display the SCS-1 Line Configuration window. You must
configure each line card used in the SCS-1 or SCS-1R Receiver.
Line Number: Enter the number of the communication line assigned to the line card in the SCS-1 or
SCS-1R Receiver that you are programming. Enter a single digit from 1 to 9.
Line Type: Select the type of communication line the receiver is connected to from the Line Type
menu.
None: Select None to clear all programmed information for the line prior to programming.
Multiplex (MPX): Select this option when you are using multiplex communication through a DMP SCS-
1 Receiver using a polled communication line.
Digital Dialer (DD): Select Digital Dialer when you are using DMP's proprietary (SDLC) format for
communication over standard telephone lines through an SCS-1, SCS-1R or SCS-105 receiver.
DDMX: Select DDMX if the line card in the SCS-1 Receiver is configured for digital dialer/multiplex
accounts. You may have up to 128 DDMX accounts on one line card.
ASYNCH: Select ASYNCH if the line card is configured for asynchronous network communications.
Phone Number: Enter the phone number of the telephone line connected to the receiver.
Billing Number: Enter the billing number that the telephone company has assigned to the telephone
line connected to this line card.
Comment: Enter any comments that might assist you in billing or system maintenance.
Checkboxes 0 to 127: Select the checkbox next to the number that corresponds to each multiplex
account connected to this line card.
Repeat this process for each line card in use.
The SCS-1 Receiver must contain firmware revision level 801 or higher. If your receiver firmware level
is less than 801, contact DMP Customer Service for an SCS-1 Firmware Update kit.
If you are not sure which revision level your receiver is currently running, follow the steps below:
1. Open the front of the receiver by turning the four quick disconnect screws counterclockwise.
2. Remove the plexiglass cover and press the Processor Restart button on the far left side of the
SCS-120 Power Supply board.
The receiver restarts and displays its firmware revision level on the CRT for about three seconds