Specifications

© 2015 Digital Monitoring Products
the panel sends only a zone fault report to the central station.
Note: You cannot enable cross zoning for Fire Verify zones or for any Fire zone type that is
programmed with a retard delay.
Priority Zone: Select this box to require this zone to be in a normal condition before its assigned area
can be armed.
Traffic Count: If selected, provides reporting to the receiver of the number of zone trips per area for
Night and Exit type zones while in a disarmed state. Default is NO.
Zone Audit Days (XT30/XT50 Series Version 103 or
higher): Specify the number of days, 0 to 99, allowed to elapse
without this zone being tripped before a fault message is sent.
The message is sent to the receiver(s) programmed to receive
Supervisory/Trouble Reports at 10:00 am following the
expiration of the timer. Each time the zone is tripped, the
Zone Audit Days timer restarts and begins to countdown the
number of days programmed. After the countdown expires, a
fault message is sent and the Zone Audit Days timer restarts
and begins to countdown the number of days programmed. Available for all zone types except fire and
fire verify. Enter 0 (zero) to disable this function. Default is 0 (zero). This feature is used to monitor
a zone for inactivity.
Receiver Routing (XT30/XT50 Series Version 103 or higher): If Auxiliary 1 or Auxiliary 2 is
selected as Zone Type, select from the following routing options:
Normal: Sends Alarm and Supv/Trbl messages from this zone to receiver 1 or receiver 2 as
programmed.
1: Sends Alarm and Supv/Trbl messages from this zone to receiver 1 only, regardless of the
programming for that receiver.
2: Sends Alarm and Supv/Trbl messages from this zone to receiver 2 only, regardless of the
programming for that receiver.
Both: Sends Alarm and Supv/Trbl messages from this zone to both receivers, regardless of the
programming for either receiver.
Real-time Status: If selected, this allows Real-time Status reports, such as Door Open or Closed with
zone number or output condition, to be sent using PC Log reporting. Selecting NO disables Real-time
Status for this zone. Default is no.
Door Number: If Real-time Status is selected, enter a door number (keypad bus address) of 1-16 for
XR500 systems or 1-8 for XR100 systems. When a door number is selected, the door number is
included in the status report instead of the zone number. Enter 0 (zero) to disable this feature and
report the zone number. Default is 0 (no door).
Program > Ho liday Dates
The Holiday Dates window allows you to enter dates that are used by the Holiday Schedules to override
daily schedules.
Number: Assign a number to the holiday date. You may assign up to 20 holiday dates.
Name: Enter up to 32 characters for the name of the holiday.