the panel sends only a zone fault report to the central station.
Note: You cannot enable cross zoning for Fire Verify zones or for any Fire zone type that is
programmed with a retard delay.
Priority Zone: Requires this zone to be in a normal condition before arming its assigned area.
Fire Panel Slave: This option is available on Fire Zones (FI) only and allows a fire zone the ability to
provide slave communication operation for a separate fire alarm control panel. If selected, this zone
will transmit a restoral immediately when restored by the fire panel being monitored. A sensor reset is
not required to generate the restoral message.
If not selected, this zone will operate as a standard fire type zone and a sensor reset is required
before the zone will return to normal.
Traffic Count (XT Series, XR150/XR350/XR550 Series Version 109 or higher): This option is
only displayed for Night (NT) and Exit (EX) type zones. If selected, provides reporting to the receiver
of the number of zone trips per area while in a disarmed state.
Traffic Count - Virtual Keypad, (XT Series Version 122 or higher, XR150/XR350/XR550 Series
Version 109 or higher): Traffic Count data for the 10 lowest numbered zones with Traffic Count set
to YES will also be reported to the Virtual Keypad App if enabled at vk.securecomwireless.com. Default
is NO.
Zone Audit Days (XT30/XT50 Series Version 103 or higher; XTL, XTLN, XTLN-WiFi, XR100/
XR500 Series Version 205 or higher, XR150/XR350/XR550 Series): Specify the number of days,
0 to 99 for XT Series or 0-365 for XR100/500 Series or XR150/XR350/XR550 Series, allowed to elapse
without this zone being tripped before a fault message is sent. The message is sent to the receiver(s)
programmed to receive Supervisory/Trouble Reports at 10:00 am following the expiration of the
timer. Each time the zone is tripped, the Zone Audit Days timer restarts and begins to countdown the
number of days programmed. After the countdown expires, a fault message is sent and the Zone Audit
Days timer restarts and begins to countdown the number of days programmed. Available for all zone
types except fire and fire verify. Enter 0 (zero) to disable this function. Default is 0 (zero). This
feature is used to monitor a zone for inactivity.
Receiver Routing (XT30/XT50 Series Version 103 or higher, XTL, XTLN, and XTLN-WiFi): If
Auxiliary 1 or Auxiliary 2 is selected as Zone Type, select from the following routing options:
Normal: Sends Alarm and Supv/Trbl messages from this zone to receiver 1 or receiver 2 as
programmed.
1: Sends Alarm and Supv/Trbl messages from this zone to receiver 1 only, regardless of the
programming for that receiver.
2: Sends Alarm and Supv/Trbl messages from this zone to receiver 2 only, regardless of the
programming for that receiver.
Both: Sends Alarm and Supv/Trbl messages from this zone to both receivers, regardless of the
programming for either receiver.
Real-time Status (XR500 Series/XR100 Series Version 203 or higher): If selected, this allows
Real-time Status reports, such as Door Open or Closed with zone number or output condition, to be
sent using PC Log reporting. Selecting NO disables Real-time Status for this zone. Default is NO.
Door Number (XR150/XR350/XR550 and XR100/XR500 Series Version 203, 204 or 205): If
Real-time Status is selected, enter a door number (keypad bus address) of 1-16 for XR500 systems or
1-8 for XR100 systems. When a door number is selected, the door number is included in the status
report instead of the zone number. Enter 0 (zero) to disable this feature and report the zone number.
Default is 0 (no door).