Specifications

© 2015 Digital Monitoring Products
XT Series Advanced Tab XR150/XR350/XR550 Series Advanced Tab
Swinger Bypass (XR150/XR350/XR550, XR100/XR500): Allows the zone to be bypassed by the
panel according to the specifications programmed in Swinger Bypass Trips and Swinger Reset in the
System Options window.
Swinger Bypass (XT30/XT50, XTL, XTLN, XTLN-WiFi): Allows the zone to be bypassed by the panel
after two alarms, troubles, or local trips within one hour. The bypass condition displays in the keypad
Status List.
Retard: Programs the zone to operate with the zone retard delay as specified in the Retard Delay field
in the System Options window. Zone retard functions only in zone short conditions. The zone must
remain shorted for the full length of the retard delay before the panel recognizes the shorted
condition. If the arming zone has Maintain as the style, the retard delay also occurs when the zone
returns to a normal state.
Fast Response: Provides a zone response time of 327ms. Leave this field blank to provide a normal
zone response time of 500ms. LX-Bus zones have a fixed response time of 200ms.
Cross Zone: Enables cross zoning for this zone. Cross zoning requires one or more armed zones to
fault within a programmed time before an alarm report is sent to the central station. The length of the
programmed time is designated in the Cross Zone Seconds field in Program > System Options.
Note: To operate correctly, all cross-zone zones need to be programmed as the same zone
type.
When a cross-zoned zone trips, the bell action assigned to the zone activates and the cross-zone time
specified in Program > System Options begins to count down. If another cross-zoned zone faults or if
the first zone restores and faults again before a sensor reset is performed, the panel sends an alarm
report to the central station. If no other cross-zoned zones trip before the cross-zone time expires,